Sažetak

The paper presents some results of the investigation of stray losses in power transformers that are caused by high-current loops. The investigation was focused on: a) additional losses in tank cover around high-current bushings and the way of their reduction, b) extra leakage flux and additional losses due to high-current delta-connections. The insertion of nonmagnetic gaps between the phase bushings reduces the extra cover losses more than three times. A nonmagnetic plate around the high-current bushings reduces these extra losses practically to zero. The extra losses due to the high-current delta-connections could be significant for the transformer loss level. These extra losses could be controlled (reduced) by the design layout of the delta-connections.

Ključne riječi

transformer stray losses high currents