Algorithm Based on Cascade Control with PI Controllers for Water-Based Cooling System in Data Centre

Krešimir Osman, Trpimir Alajbeg, Vanja Jug

Sažetak

The paper presents a control algorithm for a water-based cooling system with a chiller and cooling tower in a data centre located within a commercial building. The control algorithm is implemented based on a mathematical model of the system. The system operates on the water-cooling principle and consists of two circuits. In the chilled-water circuit, the evaporator side supplies water at 18/26∘C for direct rack cooling within the data centre. In the second circuit, operating at 27/32 °C, heat is removed from the condenser side via a cooling tower. The control algorithm uses a cascade control architecture with both loops regulated by PI controllers. The paper also includes simulations using a combination of MATLAB Simulink and SimScape Fluids software tools for water outlet temperatures, as well as the coefficient of performance over time.

Ključne riječi

cascade control PI algorithm cooling system chiller cooling tower data center